Instructions: back to home page
- Print
these pages.
- Circle
the correct answers.
- Page
down to the last page for the verification forms and mailing instructions.
NEC code 90 question correspondence
course based on the 2005 NEC.
1-25 Questions:
Understanding the NEC
- When
rigid metal conduit is threaded in the field, a standard die with _____
shall be used.
- 3/4 in. taper per foot
- 1 in. taper per foot
- 1/16 in. taper per foot
- no taper
344.28
- Nails
or screws can fasten boxes to structural members of a building using
brackets on the outside of the enclosure, or they can pass through the
interior within _____ of the back or ends of the enclosure. Screws are not
permitted to pass through the box unless exposed threads in the box are protected
using approved means to avoid abrasions of conductor insulation.
- 1/8 in.
- 1/16 in.
- 1/4 in.
- 1/2 in.
314.23(B)(1)
- IMC
shall be firmly fastened within _____ of each outlet box, junction box,
device box, fitting, cabinet, or other conduit termination.
- 12 in.
- 18 in.
- 2 ft
- 3 ft
342.30(A)
- Live
parts of electrical equipment operating at _____ or more shall be guarded
against accidental contact by approved enclosures or by suitable
permanent, substantial partitions, or screens arranged so that only
qualified persons have access to the space within reach of the live parts.
- 20V
- 30V
- 50V
- 100V
110.27(A)(2)
- Handhole
enclosures shall be designed and installed to withstand _____.
- 3,000 lb
- 6,000 lb
- all loads likely to be
imposed
- 600 lb
314.30
- When
ENT is installed concealed in walls, floors, and ceilings of buildings
exceeding three floors above grade, a thermal barrier shall be provided
having a minimum _____-minute finish rating as listed for fire-rated
assemblies.
- 5
- 10
- 15
- 30
362.10(2)
- •When
installing raceways underground in rigid nonmetallic conduit and other
approved raceways, there shall be a minimum of _____ of cover.
- 6 in.
- 12 in.
- 18 in.
- 22 in.
Table 300.5, Column 3
- All
joints between lengths of ENT, and between ENT and couplings, fittings, and
boxes shall be made by _____.
- a qualified person
- set screw fittings
- an approved method
- exothermic welding
362.48
- Raceways
or cable trays containing electric conductors shall not contain any pipe, tube,
or equal for steam, water, air, gas, drainage, or any service other than
_____.
- as allowed by the
authority having jurisdiction
- electrical
- pneumatic
- as designed by the
engineer
300.8
- Underground
raceways and cable assemblies entering a handhole enclosure shall extend
into the enclosure, but they are not required to be _____.
- bonded
- insulated
- mechanically connected to
the handhole enclosure
- below minimum cover
requirements after leaving the handhole
314.30(B)
- The
number of conductors allowed in ENT shall not exceed that permitted by the
percentage fill specified in _____.
- Chapter 9, Table 1
- Table 250.66
- Table 310.16
- 240.6
362.22
- Raceways,
cable trays, cable bus, auxiliary gutters, cable armor, boxes, cable sheathing,
cabinets, elbows, couplings, fittings, supports, and support hardware
shall be of materials suitable for _____.
- corrosive locations
- wet locations
- the environment in which
they are to be installed
- none of these
300.6
- In the
event the NEC requires new products, constructions, or materials that are
not yet available at the time a new edition is adopted, the _____ may
permit the use of the products, constructions, or materials that comply
with the most recent previous edition of this NEC adopted by the
jurisdiction.
- electrical engineer
- master electrician
- authority having
jurisdiction
- permit holder
90.4
- Equipment
listed by a qualified electrical testing laboratory is not required to
have the factory-installed _____ wiring inspected at the time of installation
except to detect alterations or damage.
- external
- associated
- internal
- all of these
90.7
- Type
TC cable can be used _____.
- for power and lighting
circuits
- in cable trays in
hazardous (classified) locations
- in Class 1 control
circuits
- all of these
336.10
- For
grounded systems, the electrical equipment and wiring, and other
electrically conductive material likely to become energized, are installed
in a manner that creates a permanent, low-impedance circuit capable of
safely carrying the maximum ground-fault current likely to be imposed on
it from where a ground fault may occur to the _____.
- ground
- earth
- electrical supply source
- none of these
250.4(A)(5)
- Concrete,
brick, or tile walls are considered as _____, as it applies to working space
requirements.
- inconsequential
- in the way
- grounded
- none of these
110.26(A)(1) and Table 110.26(A)(1),
Condition 2
- Electrical
systems that are grounded shall be connected to earth in a manner that will _____.
- limit voltages due to lightning,
line surges, or unintentional contact with higher voltage lines
- stabilize the
voltage-to-ground during normal operation
- facilitate overcurrent
protection device operation in case of ground faults
- a and b
250.4(A)(1)
- The
grounding conductor connection to the grounding electrode shall be made by
_____.
- listed lugs
- exothermic welding
- listed pressure connectors
- any of these
250.70 and 250.8
- Metallic
boxes are required to be _____.
- metric
- installed
- grounded
- all of these
314.4
- The wiring
contained inside which of the following are required to be accessible?
- Outlet boxes
- Junction boxes
- Pull boxes
- all of these
314.29
- When threadless couplings and connectors used in the
installation of RMC are buried in masonry or concrete, they shall be of
the _____ type.
- raintight
- wet and damp locations
- nonabsorbent
- concrete-tight
344.42(A)
- The
following systems shall be installed in accordance with the NEC:
- signaling
- communications
- power and lighting
- all of these
90.2(A)
- EMT shall
not be used where _____.
- subject to severe physical
damage
- protected from corrosion
only by enamel
- used for the support of
luminaires
- any of these
358.12
- The
grounding electrode conductor is the conductor used to connect the
grounding electrode to the equipment grounding conductor and the grounded
conductor at _____.
- the service
- each building or structure
supplied by feeder(s)
- the source of a separately
derived system
- all of these
100 Grounding Electrode Conductor
26-50
Questions: Understanding the NEC
- All
threaded conduits or fittings referred to in hazardous (classified)
locations shall be threaded with a _____ taper per foot.
- ½ in.
- ¾ in.
- 1 in.
- all of these
500.8(D)
- A
Class III, Division_____ location is where easily ignitible
fibers or combustible flying material are stored or handled but not
manufactured.
- 1
- 2
- 3
- all of these
500.5(D)(2)
- Audio
system equipment supplied by branch-circuit power shall not be located
within _____ of the inside wall of a pool, spa, hot tub, fountain, or
tidal high-water mark.
- 2 ft
- 10 ft
- 5 ft
- 18 in.
640.10(A)
- Conduits,
cable trays, and open wiring used for intrinsically safe systems shall be
identified by permanently affixed labels with the wording "Intrinsic
Safety Wiring." The labels shall be visible after installation and
the spacing between labels shall not exceed _____ ft.
- 3
- 10
- 25
- 50
504.80(B)
- For
listed explosionproof equipment, factory
threaded entries shall be made up with at least _____ threads fully
engaged.
- 4
- 4½
- 5
- 6
500.8(D) Ex
- No
seal is required if a conduit (without unions, couplings, boxes, or
fittings) passes completely through a Class I, Division 2 location if the
termination points of the unbroken conduit are in unclassified locations
and it has no fittings less than _____ beyond each boundary of the
classified location.
- 6 in.
- 12 in.
- 18 in.
- 24 in.
501.15(B)(2) Ex 1
- Conductors
and cables of intrinsically safe circuits not in raceways or cable trays shall
be separated by at least _____ and secured from conductors and cables of
any nonintrinsically safe circuits.
- 6 in.
- 2 in.
- 18 in.
- 12 in.
504.30(A)(3)
- In
Class I, Division 1 locations, all apparatus and equipment of signaling,
alarm, remote-control, and communications systems, _____, shall be
identified for Class I, Division 1 locations.
- above 50V
- above 100 volts-to-ground
- regardless of voltage
- except under 24V
501.150(A)
- Intrinsically
safe and associated apparatus are permitted to be installed in _____.
- any hazardous (classified)
location for which they have been identified
- Class I locations
- Class II locations
- Class III locations
504.10(B)
- In
hazardous (classified) locations, intrinsically safe apparatus shall _____
in the hazardous (classified) location in accordance with 250.100.
- be secured
- be bonded
- be painted
- not be used
504.60(A)
- Class
II locations are those that are hazardous because of the presence of
_____.
- combustible dust
- easily ignitible
fibers or flyings
- flammable gases or vapors
- flammable liquids or gases
500.5(C)
- ITC-HL
cables with a gas/vaportight,
continuous-corrugated metallic sheath, an overall jacket of suitable
polymeric material, and provided with termination fittings listed for the application
can be installed in Class I, Division 1 _____ establishments with
restricted public access.
- commercial
- industrial
- institutional
- all of these
501.10(A)(1)(d)
- Boxes
and fittings used for taps, joints, or terminal connections shall be _____
where installed in Class II, Division 1 hazardous (classified) locations.
- explosionproof
- identified for Class II
locations
- dusttight
- weatherproof
502.10(A)(1)(4)
- Intrinsically
safe conduit or cable runs that leave a Class I or II location shall be
sealed. The seal shall be _____.
- explosionproof
or flameproof
- flameproof
- a and b
- none of these
504.70
- Equipment
is required to be identified not only for the class of location but also
for the explosive, combustible, or ignitible properties
of the specific _____ that will be present.
- gas or vapor
- dust
- fiber or flyings
- all of these
500.8(A)(1)
- Electrical
equipment installed in hazardous (classified) locations shall be
constructed for the class, division, and group. An atmosphere containing
_____ is classified as Group C.
- hydrogen
- ethylene
- propylene oxide
- all of these
500.6(A)(3) FPN
- An
assembly of interconnected intrinsically safe apparatus, associated
apparatus, and interconnecting cables designed so that those parts of the
system used in hazardous (classified) locations are intrinsically safe
circuits is a(n) _____.
- intrinsically safe system
- safe location
- reclassified location
- associated system
504.2
- Loudspeakers
of a permanent audio system which are installed in a fire-resistance rated
partition, wall, or ceiling shall be listed for the purpose or installed
in an enclosure or recess that _____.
- maintains the
fire-resistance rating
- is no more than 4 in. deep
- is no more than 6 ft 6 in.
high
- all of these
640.25
- All
threaded conduits or fittings referred to in hazardous (classified)
locations shall be made wrenchtight in order to
_____.
- prevent sparking when a
fault current flows
- ensure the explosionproof or flameproof integrity of the conduit
system
- a and b
- none of these
500.8(D)
- Conductors
of intrinsically safe circuits shall not be placed in any _____ with
conductors of any nonintrinsically safe system.
- raceway
- cable tray
- cable
- any of these
504.30(A)(1)
- Raceways
permitted as a wiring method in Class II, Division 2 hazardous
(classified) locations include _____.
- rigid metal conduit and
intermediate metal conduit
- electrical metallic tubing
- rigid nonmetallic conduit
- a or b
502.10(B)(1)
- Audio
cables installed exposed on the surface of ceilings and walls shall be
supported by the structural components of the building in such a manner
that the cable will not be damaged by normal building use. Such cables
shall be supported by _____ designed and installed so as not to damage the
cable.
- straps
- staples
- hangers
- any of these
640.6
- Audio
system equipment (speakers) powered by a listed Class 2 power supply, or
by the output of an amplifier listed for use with Class 2 wiring, shall
only be restricted in its placement by _____.
- the manufacturer's
recommendations
- 640.10(A), within 6 ft of
water
- the local authority having
jurisdiction
- the desires of the owner
640.10(B)
- When
seals are required for Class I locations, they shall comply with the
following rule(s):
- They shall be listed for
Class I locations and shall be accessible.
- The minimum thickness of the
sealing compound shall not be less than the trade size of the sealing
fitting and, in no case, less than 5/8 in.
- Splices and taps shall not
be made in the conduit seal.
- all of these
501.15(C)(1), (2), (3), and (4)
- Raceways
permitted as a wiring method in Class II, Division 1 hazardous
(classified) locations include _____.
- threaded rigid metal
conduit and intermediate metal conduit
- rigid nonmetallic conduit
- electrical metallic tubing
- any of these
502.10(A)(1)
51-75
Questions: Basic Electrical Theory
- Providing
a path to the earth often helps reduce electrostatic charge.
A. True
B. False
- Ferrous
metals contain iron, therefore they cannot be magnetized.
A. True
B. False
- The
severity of an electric shock is dependent on the current flowing through
the body, which is impacted by circuit voltage and contact resistance.
A. True
B. False
- Ohmmeters
measure the _____ or opposition to current flow of a circuit or component.
- voltage
- current
- power
- resistance
- A
holding relay is primarily used for worker convenience.
A. True
B. False
- The
best conductors, in order of their conductivity, are: gold, silver,
copper, and aluminum.
A. True
B. False
- What
is the power loss in watts of a conductor that carries 24A and has a
voltage drop of 7.2V?
- 175W
- 350W
- 700W
- 2,400W
- What
is the conductor power loss in watts for a 120V circuit that has a 3
percent voltage drop and carries a current flow of 12A?
- 43W
- 86W
- 172W
- 1,440W
- Kirchoff’s
Voltage Law states that in a series circuit, the sum of the voltage drops
across all of the resistors will equal the applied voltage.
A. True
B. False
- When
power supplies are connected in parallel, the voltage remains the same,
but the current or amp-hour capacity will be increased.
A. True
B. False
- Improper
wiring or mishandling of multiwire branch circuits can cause
_____ connected to the circuit.
- overloading of the ungrounded
conductors
- overloading of the
grounded (neutral) conductors
- destruction of equipment
because of overvoltage
- b and c
- Metal
parts of premises wiring must be bonded to a low-impedance path designed
so that the circuit protection device will quickly open and clear a ground
fault.
A. True
B. False
- Inverse-time
breakers operate on the principle that as the current decreases, the time
it takes for the device to open decreases.
A. True
B. False
- Factors
that impact the available short-circuit current
include transformer _____.
- voltage
- kVA
rating
- impedance
- all of these
- Equipment
must have a(n) _____ current rating that permits
the protection device to clear a short circuit or ground fault without extensive
damage to the components of the circuit.
- overload
- short circuit
- ground fault
- b or c
- Severe
electric shock or death can occur if a person touches the ungrounded and
the grounded (neutral) conductors at the same time, even if the circuit is
GFCI protected.
A. True
B. False
- An
AFCI protection device provides protection from an arcing fault by
recognizing the characteristics unique to an arcing fault and by
functioning to de-energize the circuit when an arc fault is detected.
A. True
B. False
- Even
when power is removed from the circuit, capacitors can store large amounts
of energy for a long period of time. They can discharge and arc if
inadvertently shorted or grounded out.
A. True
B. False
- The expanding
and collapsing magnetic field within the conductor induces a voltage in
the conductors (CEMF) that repels the flowing electrons toward the surface
of the conductor. This is called _____.
- eddy currents
- induced voltage
- impedance
- skin effect
- AC inductive
or capacitive reactive loads cause the voltage and current to be in-phase
with each other.
A. True
B. False
- Dual-voltage
ac motors are made with two field windings. The field windings are
connected in _____ for low-voltage operation and in _____ for high-voltage
operation.
- series, parallel
- parallel, series
- series, series
- parallel, parallel
- If
the rotating part of the motor winding is jammed so that it cannot rotate,
no CEMF will be produced in the motor winding. Result—the motor operates
at _____ and the windings will be destroyed by excessive heat.
- FLA
- FLC
- LRC
- any of these
- Swapping
_____ of the line conductors can reverse a 3Ø ac motor’s rotation.
- one
- two
- three
- none of these
- Voltage
induced in the secondary winding of a transformer is dependent on the
number of secondary turns as compared to the number of primary turns.
A. True
B. False
- Three-phase,
_____ wye-connected systems can overheat because
of circulating odd triplen harmonic currents.
- 2-wire
- 3-wire
- 4-wire
- none of these
76-90
Questions: Low-Voltage and Power-Limited Systems
- Class
2, Class 3, and PLTC cable not terminated at equipment and not identified
for future use with a tag is considered abandoned.
A. True
B. False
725.2
- Class
1, 2, and 3 cables installed _____ to framing members shall be protected
against physical damage from penetration by screws or nails by 1¼ in.
separation from the framing member or by a suitable metal plate in accordance
with 300.4(D).
- exposed
- concealed
- parallel
- all of these
725.8
- All
wiring for Class 1 circuits shall be installed in accordance with Article
300 and the other appropriate articles in Chapter 3.
A. True
B. False
725.25
- Conductors
of Class 2 and Class 3 circuits shall not be placed in any enclosure,
raceway, cable, or similar fittings with conductors of Class 1 or electric
light or power conductors, except when they are _____.
- insulated for the maximum
voltage present
- totally comprised of
aluminum conductors
- separated by a barrier
- all of these
725.55(B)
- Class
2 or Class 3 cables, installed in vertical runs penetrating more than one
floor or installed in a shaft, shall be type _____.
- CL2R
- CL3R
- CL2P
- any of these
725.61(B)
- Type ITC
cable is permitted to be installed with power, lighting, and Class 1
circuits.
A. True
B. False
727.5
- All
accessible portions of abandoned fire alarm cable shall be removed.
A. True
B. False
760.3(A)
- Fire
alarm circuits shall be identified at all terminal and junction locations
in a manner that will unintentional interference with the signaling
circuit during _____.
- installation
- testing and servicing
- renovations
- all of these
760.10
- Nonpower-limited fire
alarm circuit conductors of sizes _____ shall be of the types included in
760.27(B) or other types of insulation listed for nonpower-limited
fire alarm circuit use. Conductors larger than 16 AWG shall comply with
Article 310.
- 16 and 18 AWG
- 14 and 12 AWG
- 14 AWG and larger
- all of these
760.27(B)
- The
listing requirements for power-limited fire alarm (PLFA) circuit sources
are found in Tables 12(A) and 12(B) of _____.
- Article 760
- Chapter 9
- Article 300
- Annex C
760.41 FPN No. 1
- Power-limited
fire alarm (PLFA) cables can be supported by strapping, taping, or
attaching to the exterior of a conduit or raceway.
A. True
B. False
760.58
- Conductive
optical fiber cables contain noncurrent-carrying conductive members such
as metallic _____.
- strength members
- vapor barriers
- armor or sheath
- any of these
770.9(B)
- Where
exposed to contact with electric light or power conductors, the
noncurrent-carrying metallic members of optical fiber cables entering
buildings shall be _____.
- grounded as close to the
point of entrance as practicable
- interrupted as close to
the point of entrance as practicable by an insulating joint or equivalent
device
- a or b
- a and b
770.93
- Type
OFNG, OFN, OFCG, and OFC optical fiber cables may be used as risers when
_____.
- encased in a metal raceway
- located in a fireproof
shaft having a firestop at each floor
- a or b
- none of these
770.154(B)(2)
- All
accessible portions of abandoned communications cable shall be removed.
A. True
B. False
800.3(C)
To obtain your Continuing
Education Credits follow the below instructions.
- Print
out first.
- Fill
in all fields applicable.
- Include
your certification or license number.
- We’ll
take care of crediting with the state and mailing back to you the quiz
results.
Send by mail
- Test
& answer sheets.
- Fill
out this form below completely.
- Applicable
fees by check payable to Gary Klinka.
- Mail to: Gary Klinka at 228 Mandella Ct Neenah
WI 54956.
- Questions call: 920-727-9200 office and fax or
920-740-6723 cell garyklinka@hotmail.com
----------------------------Educational Course
Attendance Verification Form ------------------------
Attendee’s Name
Date
Address
Credential Number
Phone#
Course Title and Name Nec
90 Quiz
List the name of each credential held by attendee
Credited Hours 3
hrs
Email address
Fax#
--------------------------------------------------------------------------------------------------------
To be completed by Gary Klinka
www.garyklinka.com My credential link #70172
Course Password
Course ID# 8257
Attendee passed the course with a greater than 70% score on
Date
Instructor Signature